PRODUCTS LIST
Home > Product Show
|
EKI-1242IECMS-A工業(yè)協(xié)議網(wǎng)關(guān)
Product Numbers: 2023101115347
Price: US $
Product description:EKI-1242IECMS-A工業(yè)協(xié)議網(wǎng)關(guān)
|
|
INTRODUCTION
EKI-1242IECMS-AModbus RTU/TCP to EtherCAT Fieldbus Gateway
- Wide Temperature
Seamless integrate Modbus RTU/TCP and EtherCAT communication
Built-in real time diagnostic to increase highly efficiency of device management
Designed for protocol extensibility and adaption
Modbus TCP Master mode supports 64 connections
Supports dual power input for power redundancy
Mounts on DIN-rail and Wall mount
詳細(xì)規(guī)格
Power Consumption 5.2W (system)
Power Input (DC) 12 ~ 48 VDC
Power Operating Current 0.22 @ 24V ; 0.11 @ 48V
Serial Port Number 2
Data Bits 7, 8
Stop Bits 1, 2
Parity None, Odd, Even, Space, Mark
Serial Signals RS-232: TxD, RxD, CTS, RTS, DTR, DSR, DCD, RI, GND
RS-232 Yes
RS-422 Yes
RS-485 Yes
Serial Port Connector Type DB9 male
Serial Transmission Speed 50 ~ 921.6 kbps, any baud rate setting
Flow Control XON/XOFF, RTS/CTS, DTR/DSR
Modbus RTU/TCP Mode Client
Modbus RTU/TCP Functions Support 1, 2, 3, 4, 5, 6, 15, 16, 23
Modbus RTU/TCP Max. No. of Connections 64 connections
EtherCAT Max. Total I/O Data Size (SDO&PDO objects)
EtherCAT Inout 512 bytes
EtherCAT Outout 512 bytes
EtherCAT Fmmu Channel 4
Temperature (Storage Range) -40 ~ 85°C (-40 ~ 185°F)
Humidity (Operating Range) 10~90% RH non-condensing (refer to IEC 60068-2-3)
Temperature (Operating Range) -40 ~ 75°C (-40 ~ 167°F)
Temperature (Min. Operating) -40°C (-40°F)
Temperature (Max. Operating) 75°C (167°F)
RJ-45 Transmission Speed 10/100 Mbps
RJ-45 Port Number 4
RJ-45 Port Connector Type RJ-45
Ethernet Standard IEEE 802.3 , 802.3ab , 802.3u
EMC CE, FCC Class A
EMI EN 55011/ EN 55022 Class A, EN 61000-6-4, FCC Part 15 Subpart B Class A
EMS EN 61000-4-2 (Level 4), EN 61000-4-3 (Level 3), EN 61000-4-4 (Level 4), EN 61000-4-5 (Level 4), EN 61000-4-6 (Level 3), EN 61000-4-8 (Level 4)
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6
Modbus RTU/TCP Functions Support 1,2,3,4,5,6,15,16,23
Modbus RTU/TCP Mode Client
Modbus TCP Yes
Modbus RTU Yes
EtherCAT Yes
Ethernet Yes
Modbus ASCII Yes
|